PV Input Data Max. Input Power(W) | 15000 | Max. lnput Voltage(V) | 1000 | MPPT OperatingVoltage Range/Nominal lnput Voltage(V) | 180-900/610 | Max. Input Current(A) | 18/18 | Max. Short Circuit Current(A) | 20/20 | Number of MPPT Trackers | 2 | Number of Strings per MPPT | 1/1 | Battery Data Operating Voltage Range(V) | 179.2~233.6 | Battery model | KY-E51V100AH-A00 | Nominal Charge/Discharge Current(A) | 50/50 | Max.Charge/Discharge Current(A) | 65/65 | Number of Batteries | 4 | Single Battery Capacity(kwh) | 5.12 | Nominal Capacityl(kwh) | 20.48 | Available Capacity(kwh) | 18.43 | AC Output Data(GRID) Nominal Output Power(W) | 10000 | Max. Apparent Power (VA) | 11000 | Max Input Power(W) | 18000 | Nominal Output Voltage(Vac) | 380/400V,3L/N/PE | Nominal Output Frequency(Hz) | 50/60 | Max. Output Current(A) | 16 | Max. Three phase Unbalanced Output Current(A) | 22 | Grid Bypass Current(A) | 35 | Power Factor | ~1 (0.8 lead to 0.8 lag can be set) | Total Harmonic Distortion(%) | <3 | AC Output Data(EPS) Nominal Output Power(W) | 10000 | Max. Apparent Power (VA) | 11000 | Nominal Output Voltage(Vac) | 380/400V,3L/N/PE | Nominal Output Frequency(Hz) | 50/60 | Max. Three phase Unbalanced Output Current(A) | 22 | Max. Output Single phase Apparent Power(VA) | 5000 | Peak Output Apparent Power(VA)(60s) | 12000 | Peak Output Apparent Power(VA)(10s) | 15000 | On/off Grid switching time(ms) | / | AC Output Data(GEN) Nominal Voltage(Vac) | 380/400V,3L/N/PE | Nominal Frequency(Hz) | 50/60 | Nominal Input Apparent Power(VA) | 10000 | Temperatue Control System Temperatue Control System | Constant temperature and humidity air conditioner | Fire Fighting System Active | Detector+Condensed aerosol fre extinguishing device | Passive | Condensed aerosol fire extinguishing device | General Data Operating Temperature Range (°C) | -25~60(>45 derating) | Altitude(m) | <4000 | Ingress Protection Rating | IP54 | Relative Humidity(%) | 0~95, No condensation | Dimension(W*H*D)(mm) | 650*1680*850 | Certification Safety Standards | IEC62109-1/-2 | EMC Standards | EN61000-6-1/-3,IEC61000 | On-grid Standard | AS4777.2:2020,NRS097-2-1:2017,EN 50549-1 for Czech,VDE-AR-N 4105:2018,EN50549-1:2019+AC:2,G98 G99,OVE-R25,EN50549-1:2019 for Poland A&B |
|